Passar para o conteúdo principal
China | 中国
Germany | Deutschland

Approvals & Standards

IEC 60282-1

  • VDE 0670 part 4
  • VDE 0670 part 402
  • DIN 43625

Key features & benefits

Mersen HV fuse-links have been used for reliable protection in high-voltage switchgear and controlgear and high-voltage systems for decades.~Limitor®-PD HV fuses are back-up fuses as defined in the standards: IEC 60282-1 and VDE 0670 T402 and dedicated to protect transformers against effects of short-circuit currents.~The VDE 0670 T402 defines fuses between 6.3A and 160A, for other ratings, thanks to consult Limitor®-P HV fuses range.~To guarantee high quality, Mersen uses the best materials: fuse-elements are in pure silver, caps are in copper coated with silver and bodies are in ceramic.

More specifications

Applications

HV Transformer protection

Product Specifications

Número de item

A1000247  

Catalogue No.

45DB120V63PD  

Descrição do item (ERP)

H 1209P BCKUP VDE292-65/63  

Description

HV fuse, DIN 43625 , VDE0670 T402, 12kV 63A, 292mm, 45mm, medium striker 80N  

Código EAN / UPC

3605340456356  

Tensão nominal AC IEC

12   kV

Ampere Rating

63   A

Tamanho do fusível

d=65mm, L=292mm  

Montagem

Clip  

Clearing I2t At Rated Voltage

63   kA²s

AC Max I.R./Breaking Capacity: I1

80   kA

Min Interrupting Rating (MBC)

220   A

Power Dissipation at Rated Current Value

60   W

Sistema de Indicação

Yes  

Tipo de sistema de indicação

Striker  

Connection/Terminal Material

Silver-Plated Copper  

Conexão / Tipo de Terminal

Cylindrical  

Corpo / Material Isolante

Ceramic  

Peso do Produto

2.2   kg

Diâmetro do produto

65   mm

Comprimento do produto

358   mm

Quantidade do pacote de venda

1   EACH

Vender o peso do pacote

2.2   kg

Vender a largura do pacote

67   mm

Vender Comprimento do Pacote

67   mm

Vender a altura do pacote

390   mm